Test hmanrua: AC hipot test system .
1. A rilru a buai em em a, a rilru a hah em em bawk a.
2. A rilru a hah lutuk chuan a rilru a buai em em a, a rilru a hah lutuk chuan a rilru a buai em em bawk.
Test hmaa inbuatsaihna .
Cable chu a normal temperature (20 ± 5℃) ah darkar 24 tal dah tur a ni a, chu chuan transportation emaw, dahkhawl lai emawa temperature stress awm thin chu a ti bo ang. Insulation resistance chu ohmmeter (2500V) hmangin teh la, value chu 100 mΩ (reference value) aia tam emaw, a tlukpui emaw a nih theih nan, a chhiatna langsar tak takte chu paih chhuak rawh.
Connection leh voltage a sang chho zel a .
Non-test phase leh metal shielding layer te hi induced voltage hlauhawmna awm lo turin rintlak takin grounded tur a ni.
Voltage chu second khatah 1 kV aia tam lo rate-in zero atanga a value tarlanah zawi zawiin tihpun tur a ni. Value tarlan a thlen hnuah minute 15 chhung enkawl tur a ni. Hemi hun chhung hian leakage current inthlak danglamna chu enfiah a ngai a ni.
Test result 100 a ni.
Test neih chhung hian breakdown leh flashover a awm lo a, leakage current chu a stable reng a (a sang lam hawi trend chiang tak a awm lo), hei hian a qualify tih a tilang. Thil dik lo a awm chuan voltage a tlahniam tur a ni a, chu chu wiring emaw cable ngei pawh a chhiatna emaw enfiah tur a ni. Fault hmanga test nawn leh khap tlat a ni.