Burden of CT PT meansurement chungchanga hriatnate chu chhui chhuak rawh

 Jul 14, 2026

 Message pakhat dah la .

 

Maintenance & Protection Engineer tan chuan Secondary Burden & 10% Error Curve Analysis chungchangah FAQ tangkai tak tak a awm a. An kaltlangin CT PT tehna chungchang kan zir belh thei a ni.

 

FAQ 1: A awlsam zawngin "Burden" tih hi eng nge ni?

Q: Engvangin nge CT Burden hi truck phurrit nen kan tehkhin?

A: CT hian delivery truck angin hna a thawk a; Burden chu kawngpui (wires/relay) "roughness" leh "weight" a ni. Impedance sang chuan CT chu voltage tam zawk siam turin a nawr a, chu chuan core saturation a thlen thin.

Physics lam chu:

• Burden sang=Secondary Voltage sang (Vs=Is * Z) a ni.

• A chhungah hian Vs sang=Magnetic Flux sang tak a awm.

Result: Burden tam lutuk hian CT chu fault laiin "lie" a siam a, reality aiin current tlem zawk report a ni.

FAQ 2: Rated Burden leh Load tak tak

Q: Ka Actual Burden hi 2.5 VA a ni a, mahse nameplate ah chuan 30 VA a inziak thung. Hei hi harsatna a ni em?

A: Ni lo, hei hi a ideal hle. Rated Burden chu a theihna sang ber a ni a; Actual Burden hi tuna kan rit zawng hi a ni. Margin lian tak tak hian dikna leh nghetna a tichiang a ni.

Tunlai Hrilhfiahna:

• Electromagnetic relay hlui hman thin 10-15 VA.

• Tunlai digital relay hian < 0.5 VA a hmang.

Value: He safety margin lian tak hian tunlai digital substation-ah CT hi rintlak zawkin a siam a ni.

FAQ 3: "10% Error Curve" awmzia.

Q: Engvangin nge 10% hi protection class CT te tan "Life-Line" a nih?

A: Error < 10% a nih chuan relay te hian hna a thawk dik hle. CT a saturate a, error chu 50-70% a tlak chuan relay chuan fault chu a hmu lo ang a, equipment chu a puak darh ta a ni.

Thutlukna siam dan Matrix:

• Error < 10%: Relay hi a hun takah a trip thin. ✅ a ni

• Error > 10%: Relay chu saturation hmangin "blinded" a ni. ❌ tih a ni

Thuhmahruai: Curve hian Maximum Allowed Burden vs. Primary Fault Current a plot a.

FAQ 4: Predictive Testing - 10,000A hmalam hun hmuh

Q: Engtin nge analyser hian current lian tak tak inject lovin 10% curve chu a hriat theih ang?

A: CT-a non-linear "Magnetic Model" hmanga siam Mathematical Extrapolation a hmang a ni.

Logic Engine chu a ni:

❶ Core Saturation tehna: Ni 2 chhunga tih tur (Excitation test).

❷ Field Burden tehna: Wire resistance tak tak a teh thin.

❸ Simulation: Computer hian 20x current-ah Vs mamawh chu a chhut chhuak thin. Vs < Saturation V a nih chuan a PASSE.

Hlawkna: Laboratory-grade safety verification hmanga system-a current stress sang-nga awm lo.

Inquiry thawn rawh .