Q: Engtin nge ka meter atan eng CT nge ka hriat ang a, eng CT nge ka relay atan?
A: CT hi specialized a ni. Meter hian load pangngaiah precision a mamawh a; relay te hian fault lian tak tak an neih laiin an mamawh a ni.
1. Metering Class hrang hrang : 1.1.
• 0.2s / 0.5s: Current 1% thlenga dik. Revenue billing atan hman a ni.
2. Invenna Class hrang hrang : 1.1.
• 5P20: Rated current vawi 20-ah 5% error a awm. Relay atan hman thin.
Thil tihsual: Invenna atan Meter CT (0.2) hmang ngai suh (a saturate ang); bill atan Protection CT (5P) hmang ngai suh (a dik tawk lo).
Ka CT hian S1, S2, S3, S4, S5 a nei a. Engtin nge ratio dik tak chu ka hmuh theih ang?
Hengte hi "Tapped" CT an ni. Connection thlak danglam hian secondary turn leh ratio a tidanglam thin.
Test dan tur: 1.1.
• Identify Common: A tlangpuiin S1 hi a awm fo thin.
• Verify Resistance: S1-S5 (turn sang ber) hian resistance sang ber a nei ang.
• Ratio Math: S1-S2 chu 100/5 (Ratio 20) a nih chuan S1-S4 chu 300/5 (Ratio 60) a ni tur a ni.
Pro Tip: Tap dang test laiin tap hman loh chu short-circuit ngai suh. I report-ah tap hman lohte chu N/C tiin mark rawh.