Cable sizing .
A hnuaia thilte hi ngaihtuah tur a ni:
A) Short circuit hmanga siam theih a ni.
b) Current continuous carrying capacity .
c) Voltage a tlahniam a, a dinhmun pangngaiah & transient condition-ah a tlahniam.
d) Electrical design criteria leh/ emaw project specification danga tarlan special operating condition eng pawh .
A, B, C, leh D atanga hriat theih tur cable lian ber chu hman tur a ni.
A) Short circuit hmanga siam theih a ni.
Cable short circuit capacity tehna atan short circuit current sang ber ngaihtuah tur a ni. Circuit breaker nena inzawm power cable short circuit condition hnuaia fault clearing hun chu a hnuaia mi ang hian chhut tur a ni:
1) Backup relay hun chhung chu a fault level sang ber a ni.
2) 0.05 Second a ni a, setting hrang hrang a awm thei.
3) Circuit breaker hnathawh hun chhung .
Power cable te chu fuse hmanga venhim a nih chuan a cut off hun tur ngaihtuah tur a ni.
b) Tuna phur thei chhunzawm zel (I0) .
Continuous current carrying capacity chu continuous conductor temperature phal chin leh cable dahna chi hrang hrangah a innghat a ni. Chu temperature chu hman a nih chuan cable termination leh a kaihhnawih hmanrua te chuan chhiatna awm lovin temperature an tuar thei tur a ni a, cable temperature avanga a lumna pawh a ti bo thei tur a ni.
c) Voltage a tlahniam .
Power cable-a voltage tlahniam zawng zawng chu full load-ah a tam berah 5%-ah tihtlem a ni ang a, motor start-naah chuan 15% aia tam a ni lo vang. He voltage drop hi main/source atanga end consumer thlengin a ni.
Nominal system voltage, component tinte impedance sang ber leh cable tinte full load current chu voltage drop calculation atan hman a ni.