I. Engvangin nge AC hian Voltage Test hi a tuar thei?
Generator stator windings te hi an hnathawh laiin electrical stress an tawk chhunzawm zel a. Rated voltage an tuar mai bakah temporary overvoltage, atmospheric surges (lightning), leh start-stop cycle tam lutuk avanga mechanical/thermal stress te pawh an tuar chhuak tur a ni.
DC leh AC Testing neih a ni ang:DC withstand test hmanrua hi portable a nih laiin leakage current data a pe thei a, mahse generator hnathawh dan tak tak chu dik takin a simulate thei lo. Generator insulation structure-ah chuan voltage hi capacitance a zirin sem darh a ni. AC test chauh hian slot-a electric stress distribution leh winding end-a corona condition te chu a simulate tak tak thei a ni.
A bul berah chuan AC withstand test hi stator insulation atana "final exam" a ni. DC testing-in a hmuh loh theih tur local defects te chu a takin a pholang a, chu chu end-turn-a insulation chhiatna, slot exit-a potential distribution inang lo, leh main insulation-a aging crack te hi a ni.
II. Tunlai Chhanna: Variable Frequency Series Resonance tih hi a ni
Hydro-generator lian emaw turbo-generator tan chuan stator winding-a equivalent capacitance (CC) hi a lian hle (a tam zawkah chuan 0.20.2 atanga 1.0 μF1.0 μF emaw a aia sang emaw a ni). Traditional power-frequency test transformer hman ni ta se, compensation inductance leh power source capacity mamawh chu a lian hle ang a, hmanrua ton engemaw zat a rit ang.
ChumiA rilru a buai em em a, a rilru a hah em em bawk aengineering lama harsatna hi a chinfel sak ta a ni. Reactor inductance (LL) leh test object capacitance (CC) inkara resonance principle hmangin a thawk a ni: f=12πL⋅Cf=2πL⋅C 1. Resonant state-ah chuan power source chuan high-voltage side-a high voltage leh current lian tak siam chhuah nan circuit-a active power loss te chu a pe chauh a ngai a ni. Hei hian equipment volume 80%80% aia tam a tihhniam phah a ni. Chubakah, he system hian inherent "fault detuning" characteristic a nei a: insulation a chhiat chuan resonant condition chu a chhe vek a, chu chuan current chu a tla nghal vek a ni. Hei hian generator core man to tak chu secondary arc chhiatna lakah a venghim a ni.
III. Core Testing kalpui dan tur
1. Inbuatsaihna (Repair aiin invenna a tha zawk) .
AC withstand test tih hmain a hnuaia thil tulte hi zawm tur a ni:
Insulation laka invenna leh Polarization Index (IR/PI/DAR) 1.1.: IR a hniam lutuk emaw, winding a hnim emaw chuan test khap tlat a ni.
DC Withstand leh Leakage Current Test a ni: Hengte hi preliminary gate anga pass a ngai.
Environment Control a ni: Relative humidity chu 75%75% hnuai lam a ni tur a ni a, winding surface te chu a fai leh vawt tur a ni.
2. Test Voltage tehna
Standard hrang hrang anginIEEE 95 a niemawGB 50150 a ni, tehfungte chu a tlangpuiin:
Handover/Commissioning Test neih a ni: Utest=(2Un+1000) VUtest =(2Un +1000) V. A rilru a hah lutuk chuan a rilru a buai em em a
Preventive Maintenance Test neih a ni: A tlangpuiin 1.5Un1.5Un emaw local utility code-in a tarlan angin emaw a ni.
Entirnan: Generator rated voltage 10.5 kV10.5 kV nei tan chuan commissioning test voltage chu 22 kV22 kV a ni tlangpui.
3. Voltage tihchak leh enkawl dan
Zero atanga tan la, voltage chu stage hrang hrangin boost rawh (a tlangpuiin target voltage 1/31/3 leh 2/32/3 ah pause la, observation atan).
Test voltage a thlen chuan maintain la forMinute 11 minute. Hemi chhung hian engineer chuan ammeter leh voltmeter te ngun takin a enfiah tur a ni a, stator chhunga discharge ri danglam tak tak awm leh awm loh a ngaithla tur a ni.
Vaukhânna Signal:Boost laiin current a san nasa hle a, a nih loh leh voltage a tlahniam nghal a, a lo let leh thei lo a nih chuan insulation a chhiat tih a tilang a ni. Fault localization (eg, corona observation emaw Partial Discharge measurement hmanga) test hi tihtawp nghal tur a ni.
Generator AC Withstand Voltage Test hi "risk sang tak, lawmman sang tak-reward" technical procedure a ni. Insulation hi a pianphungah chuan stressful tak ni mahse, generator service a luh hmaa quality barrier rintlak ber a la ni reng. Electrical engineer kan nih angin data dik tak kan zawn mai bakah volt tin hnuaia safety protocol awmte pawh kan zah tur a ni. Withstand test hlawhtling apiang hi generator hriselna atana chawimawina sang ber a ni.