A- Test tum ber:
He test hian main relay hnathawh dan test a tum a, chu chu one pakhat zel atana final setting pawm tawh angin a ni a, mahse hetah hian a tlangpuiin main function chu approved final setting tam zawkah awm tur a ni tih kan sawi a.
B- hmanrua mamawh:
1. Relay tester chu a rawn lang leh ang.
2. Multi-meter hmanga siam a ni.
3. Wire te a awm.
C- Mechanical check leh hmuh theiha enfiah:
1. Taksa lama chhiatna emaw, chhiatna emaw a awm leh awm loh enfiah.
2. Case Earth enfiah rawh.
3. Indication leh LED te enfiah thin ang che.
4. Test switch chu a hnathawh dan dik a awm leh awm loh enfiah la CT a awm chuan emaw, binary input/output isolation emaw a awm chuan.
D- phurrit test .
1. Voltage source chu 125 volt DC ah siamrem rawh.
2. Binary output deactivated zawng zawng leh binary output activation a nih chuan ammeter chhiar dan record.
3. Ammeter voltage leh reading multiply hmangin normal operation (binary output deactivated zawng zawng) leh abnormal operation (binary output activated a nih chuan) a nih chuan phurrit chu chhut rawh.
4. Relay manual-a phurrit awm tawh nen a result chu khaikhin rawh.
E- Test connection leh test dan tur:
Ka. Binary input/output check:
1. To test binary input: Input tin ah rated binary input DC voltage apply la, relay software hmangin emaw relay LCD [a awm chuan] atang emaw input dinhmun chu verify rawh.
2. To test binary output: Relay-a software hmang hian binary output chu hun engemaw chen khar turin force theih a ni a, Multi{{1}meter hmangin binary output contact resistance chu zero vel a ni tur a ni a, chu chuan binary output khar a nih thu a tarlang a ni.
II a ni. tehnate .
1. Scheme zir chianna hmanga relay-a hman thin CT ratio leh VT ratio set.
2. Freja hmangin secondary-rated voltage leh secondary{2}}rated current kan inject a.
3. Relay screen-a primary value chhiarna chu record rawh.
iii a ni. Bus bar circuit (87B) atan impedance sang tak a awm thei.
1. Relay set final setting (numerical relay-resistor metrosil) ang chuan resistor chu relay hnathawhna tur operating voltage duh ang pe turin siamrem a ngai a ni.
2. Numerical relay Setting secondary current value leh resistor value chu relay atan dah a ni a, chutah chuan relay chuan secondary current value chu multiply la, resistor chu setting voltage value nen a khaikhin ang.
– Test pick up leh drop off test tur:-3. Series resistor value chu final setting angin siam la, a value chu teh rawh.
4. Current inject la, relay operation thlengin value chu zawi zawiin tihpun rawh.
5. Series resistor atanga pickup current leh voltage te teh rawh.
– Hun test nan:
6. Relay-a normal taka open contact pakhat la la, Sverker chu (a hun takah) a siam la, setting value aiin voltage pakhat hmang rawh.
iv. Transformer danglamna (87T):
1. Transformer differential chu impedance protection hniam tak a ni a, chutah chuan current vector chu amplitude leh angle anga teh a ni a, transformer lam atanga current tehna chu differential current chhut nan a inzawm khawm a, chu chu relay-in a siam chhuah setting value a pelh chuan a ni.
A trip command a ni.
2. Pick up & drop oft test test tur chuan current inject leh a value tihsan zauh zauh a, relay operation a nih hma chuan injected current value teh la, differential leh restrain current chu chhut la, current transformer awmna hmun tin atan repeat la, relay drop off thlengin current value chu tihhniam zauh zauh la,
Current chu teh la, current transformer awmna hmun tinah repeat leh rawh.
3. Test time test: Relay atanga normally open contact pakhat chu differential protection trip atan assign la; Setting value aiin current inject tam zawk la, tripping time teh rawh.
Inquiry thawn rawh .